SUPERFIRE Z EI90 is an Automatic Fire Curtain that in the case of fire, limits and controls the fire, reduces not only radiation emission but also heat transfer creating isolation from the fabric so that protection of people and goods is maximized, with classification EI90.
The curtain is composed by two fabrics, one folds like a concertina and one flat fabric. They are both fiberglass fabric coated on both sides and seamed with reinforced steel wire and fixed to a steel roller of 78mm of diameter; galvanized steel elements as head-box, side guides and bottom bar; irrigation system on the flat fabric side. All the system is driven by a 24Vdc tubular motor and controlled by an electronic board, TRIA’s CRM (Control and Regulation for Motor) with special gravity fail safe system. The control panel for automatic curtains (CBM), with nominal input voltage of 115Vac or 220Vac and output voltage of 24Vdc. Uninterruptible Power Supply (UPS System) with autonomy up to 6 hours exists in all control panels.
Tested and approved according to the European Standards UNE EN 1634-1 and UNE EN 1363-1.